09/08
Operating Instructions ACU
237
19.2
Error Environment
The parameters of the error environment help troubleshooting both in the settings of
the frequency inverter and also in the complete application. The error environment
documents the operational behavior of the frequency inverter at the time of the last
four faults.
Error Environment
No.
Description
Function
330 DC –Link Voltage
Direct voltage in the DC link.
331
Output voltage
Calculated output voltage (motor voltage) of the
frequency inverter.
332
Stator frequency
The output voltage (motor voltage) of the fre-
quency inverter.
333 Frequency Speed Sensor 1
Calculated from the data on speed sensor 1, the
No. of pole pairs
373 and the speed sensor signal.
335 Phase current Ia
Measured current in motor phase U.
336 Phase current Ib
Measured current in motor phase V.
337 Phase current Ic
Measured current in motor phase W.
338
R.m.s current
Calculated effective output current (motor current)
of the frequency inverter.
339 Isd / reactive current
Current component forming the magnetic flux or
the calculated reactive current.
340 Isq / active current
Current component forming the torque or the cal-
culated active current.
341 Rotor magnetizing current Magnetizing current relative to the rated motor
parameters and the operating point.
342
Torque
Torque calculated from the voltage, the current
and the control variables.
343
Analog input MFI1A
Input signal on multifunctional input 1 in
Opera-
tion mode
452 - analog input.
346 Analog output MFO1A
Output signal on multifunctional input 1 in
Op-
eration mode
550 – analog.
349
Repetition frequency out-
put
Signal at repetition frequency output according to
Operation mode
550 – repetition frequency.
350 Status of digital inputs
Decimally coded status of the six digital inputs and
of multifunctional input 1 in
Operation mode
452 -
digital input.
351 Status of digital outputs
Decimally coded status of the two digital outputs
and of multifunctional output 1 in
Operation mode
550
– digital.
352 Time since release
The time of the error in hours (h), minutes (m)
and seconds (s) after the release signal:
hhhhh:mm:ss .
sec
/
10
sec
/
100
sec
/
1000
.
353 Heat sink temperature
Measured heat sink temperature.
354 Inside temperature
Measured inside temperature.
355
Controller Status
The reference value signal is limited by the control-
ler coded in the controller status.
356 Warning Status
The warning messages coded in warning status.
357 Int. value 1
Software service parameter.
358 Int. value 2
Software service parameter.
359 Long value 1
Software service parameter.
360 Long value 2
Software service parameter.
367 Warning status application The application warnings coded in warning status.
Operating Instructions ACU
237
09/08