Operating Instructions ACU
183
14.5.4 Multiplexer/Demultiplexer
The multiplexer/demultiplexer enables the transfer of various digital signals between
an overriding controller and frequency inverters via field bus or between frequency
inverters via the system bus. For parameterization of the multiplexer and demultip-
lexer using the VTable application, the commissioning and diagnosis software VPlus,
version 4.0.2 or higher is required.
Multiplexer:
The multiplexer features 16 inputs for logic signals or digital input signals.
On the output, the logic signal 927 - Output MUX for the inputs of the TxPDO process
data of the system bus or for PZDx-IN process data of the Profibus can be used.
Operation mode
Factory setting
1252 Mux inputs
7 - Off
The parameters
Mux input index (write)
1250 and
Mux input index (read)
1251 for
the input signals of the multiplexer enable parameterization via the control unit
KP500 or the application VTable in VPlus.
Parameter
Settings
No.
Description
Min.
Max.
Fact. sett.
1250 Mux input index (write)
1)
0 33 1
1251 Mux input index (read)
0
33
1
1)
Non-volatile (fixed parameterization):
Volatile:
0:
All indices in EEPROM
17
All indices in RAM
1…16: One Index of 1…16 in EEPROM
18…33: One Index of 1…16 in RAM
Note:
The setting "0" for
Mux input index (write)
1250 changes all data in
EEPROM and RAM.
In the case of non-volatile storage (0…16), the changed values are still available
when power supply is switched on again.
In the case of volatile storage (17…33), the data is only stored in RAM. If the unit is
switched off, this data is lost and the data required are loaded from EEPROM after
restart.
Demultiplexer:
The demultiplexer features an input
DeMux Input
1253
whose signal can be for the
process data RxPDO of the system bus or OUT-PZDx of Profibus.
On the output of the demultiplexer, the logic signals „910 - Output DeMux Bit 0“ to
„925 - Output DeMux Bit15“ are available, e.g. for control of FT-instructions.
Operation modes for
DeMux input
1253
9 - Zero
704 … 727 - RxPDO Word
740, 741 - Remote control word, remote state word
754 … 757 - OUT-PZD word
900 - Controller status
927 - Output MUX
Demultiplexer outputs
910 … 925 - Output DeMux Bit 0 ... output DeMux Bit 15
Operating Instructions ACU
183
09/08