04/08
Operating Instructions ACU
85
Example: BONFIGLIOLI BN 90LA Motor
Parameter
Star
Delta
370 Rated voltage
400 V
230 V
371 Rated current
3.7 A
6.4 A
372 Rated speed
1410 min
-1
1410 min
-1
374 Rated cosine Phi
0.77
0.77
375 Rated frequency
50 Hz
50 Hz
376 Rated mechanical power
1.5 kW
1.5 kW
7.2.5 Plausibility check
After the machine data (and the speed sensor data, if applicable) have been en-
tered, the calculation or examination of the parameters is started automatically. The
display changes
over to "CALC" for a short time. If the verification of the machine
data is successful, the guided commissioning procedure continues with the identifica-
tion of the parameters.
Verification of the machine data should only be skipped by experienced users. The
configurations contain complex control processes which depend to a large degree on
the correctness of the machine parameters entered.
The warning and error messages displayed during the verification process have to be
observed. If a critical condition is detected during the guided commissioning, it is
displayed by the control unit. Depending on the deviation from the expected para-
meter value, either a warning or an error message is displayed.
−
To ignore the warning or error messages, press the ENT key. The guided com-
missioning is continued. However, it is recommended that the data be checked
and corrected if necessary.
−
To correct the entered parameter values after the warning or error message,
press the ESC key. Use the arrow keys to switch to the parameter value which is
to be corrected.
Warning Messages
Code
Measures / Remedy
SA000 No warning message present. This message can be read out via an option-
al communication board.
SA001
The value of the parameter
Rated voltage
370 is out of the rated voltage
range of the frequency inverter. The maximum reference voltage is indi-
cated on the nameplate of the frequency inverter.
SA002
For a three-phase motor, the calculated efficiency is in the limit range.
Check the values entered for the parameters
Rated voltage
370,
Rated
current
371 and
Rated power
376.
SA003 The value entered for parameter
Rated cos phi
374 is outside of the nor-
mal range (0.6 to 0.95). Check the value.
SA004
For three-phase motor, the calculated slip is in the limit range.
Check the values entered for parameters
Rated speed
372 and
Rated fre-
quency
375.
Operating Instructions ACU
85
09/08