236
Operating Instructions ACU
09/08
Motor Connection
Code
Meaning
F13
00 Earth fault on output, check motor and wiring.
01
Set
IDC compensation limit
415
reached, check motor and cabling,
increase limit, if necessary.
10 Minimum current monitoring, check motor and wiring.
Control Connection
F14
01 Reference value on multifunctional input 1 faulty, check signal.
07 Overcurrent on multifunctional input 1, check signal.
30 Encoder signal defective, check connections S4IND and S5IND.
31 One track of the speed sensor signal is missing, check connections.
32 Direction of rotation of speed sensor wrong, check connections.
36
Encoder 1: Division Marks Fault. Correct
Division Marks
491 of encod-
er 1; refer to chapter 9.4.2 “Division marks, speed sensor 1”.
37
The encoder is disabled. In configurations 210, 211 and 230 an encoder
must be activated. Set parameter
Operation Mode
490 to an evalua-
tion mode (not to “0 – off). If an expansion module is installed and
parameter
Actual Speed source
766 is set to “2 – Speed Sensor 2“,
parameter
Operation Mode
493 (speed sensor 2) must be set to an
evaluation mode.
54
External error; drive responded according to parameter setting for
Op-
eration mode ext. error
535. Error was triggered via the logic signal or
digital input signal assigned to parameter
External error
183
.
Optional Components
F0A
10 Data transmission from control unit KP 500 to the frequency inverter
not possible. At least one file must be stored in the control unit.
F0B
13 The communication module was fitted to slot B without disconnection
of the mains voltage, switch mains voltage off.
In error occurrence the signal 162 - “Error Signal” is set. The signal can be linked
with inverter functions.
Output signals in error occurrence
Errors are indicated by digital signals.
162
-
Error Signal
1)
Monitoring function signals an error which is displayed in
parameter
Current Error
259.
3 -
2)
1)
For linking with inverter functions
2)
For digital output
In addition to fault messages mentioned, there are further fault messages. However
these messages are only used for internal purposes and are not listed here. If you
receive fault messages which are not listed here, please contact the BONFIGLIOLI
customer service.