09/08
Operating Instructions ACU
159
Operation mode 530,532,554
Function
21 - Comparator 2
The comparison according to the selected
Op-
eration mode
Comparator
2
543
is true.
22
- Warning V-belt
Warning of
Operation Mode
581
of V-belt moni-
toring.
23 - Timer 1
The selected
Operation Mode Timer 1
790
gen-
erates an output signal of the function.
24 - Timer 2
The selected
Operation Mode Timer 2
793
gen-
erates an output signal of the function.
25
- Warning Mask
Message of the configurable parameter
Create
Warning Mask
536.
26 - Warning, Application
Warning application is signaled. Display of the
actual value is affected via parameter
Warnings
Application
273.
27 - Warning Mask, Application
Message of the configurable parameter
Create
Warning Mask Application
626.
28
- Warning, gen + Warning,
Application
Warning or warning application is signaled.
29
- Warn. Mask, gen + Warn.
Mask, Appl.
Message of configurable parameters
Create
Warning Mask
536
and
Create Warning Mask
Application
626
.
30 - Flux-Forming finished
Magnetic field has been impressed.
41 - Brake release
Activation of a brake unit depending on the
Op-
eration Mode
620 for the starting behavior,
Op-
eration Mode
630
for the stopping behavior or
the configured brake control system.
43 - External Fan
The
Switch-On Temperature
39
has been
reached.
50 - Synchronization Fault
1)
The phase error of the index control exceeded
the
Warning limit
597
.
51 - Signal Fault
1)
Index signal period too short during index con-
trol.
56 - Phasing Done
2)
Message of phasing function. For positioning in
combination with the function of the electronic
gear, the value
Phasing: Offset
1125 was
reached.
57 - In Gear
1) 2)
Synchronization of the electronic gear is reached.
The slave drive is engaged and operates at a
synchronous angle with the master.
58 - Position comparator
2)
The current actual value is in the range between
Switch-on position
1243
and
Switch-off position
1244
of the position comparator. The adjusted
value of the parameter
Hysteresis
1245 is consi-
dered.
59 - Homing Done
2)
A reference travel operation was started and the
reference position for positioning was set.
60 - Target Position Reached
Reference orientation
469 of axle positioning
was reached or
Target position / Distance
1202 of a position-
ing
2)
operation was reached (the current act.
position is within the range set in parameter
Target window
1165 for a minimum period of
Target window time
1166).
61
- Warning Deviation of Posi-
tion
2)
The contouring error monitoring
Warning Thre-
shold
1105 was exceeded.
Operating Instructions ACU
159
09/08
Summary of Contents for Bonfiglioli Vectron ACTIVE CUBE ACU 201 Series
Page 1: ...ACTIVE CUBE Operating Instructions Frequency Inverter 230V 400V 0 25 kW 132 kW ...
Page 2: ......