14.3.2 Setting Frequency
If operation mode 4 - “Setting Frequency” is selected for a digital output, the corres-
ponding output becomes active if the actual value
Stator Frequency
210 exceeds the
value of
Setting Frequency
510
.
The relevant output is switched over again as soon as the
Stator Frequency
210
falls
below the value of “
Setting Frequency
510
minus
Setting Frequency Off Delta
517”.
Signal source 164 - “Setting Frequency” can be linked with inverter functions.
Parameter
Settings
No.
Description
Min.
Max.
Fact. sett.
510 Setting Frequency
0.00 Hz
999.99 Hz
3.00 Hz
517 Setting Frequency Off Delta
0.00 Hz
999.99 Hz
2.00 Hz
Stator Frequency
210
t
Digital output
164 - Setting Frequency
Setting Frequency Off Delta
517
Setting Frequency
510
Op. Mode Digital Output 1
530
or
4 - Setting Frequency
Op. Mode Digital Output 2
531
or
Op. Mode Digital Output 3
532
With expansion module:
Op. Mode EM-S1OUTD
533
or
Op. Mode EM-S1OUTD
534
Setting Frequency
510
Set value [Hz]
For linking with functions
164 - Setting Frequency
Operating Instructions ACU
09/08
162