158
Operating Instructions ACU
09/08
14.3
Digital Outputs
The
Operation mode Digital output 1
530 and the relay output with the parameter
Operation mode Digital output 3
532 link the digital outputs to various functions.
The selection of the functions depends on the parameterized configuration. The use
of the multifunctional output MFO1 as a digital output demands selection of an
Oper-
ation mode
550
and linking via parameter
Digital operation MFO1
554.
Operation mode 530,532,554
Function
0 - Off
Digital output is switched off.
1 - Ready or Standby Signal
Frequency inverter is initialized and on stand-by
or in operation.
2 - Run Signal
Signal enable STO (S1IND/STOA and
S7IND/STOB) and a start command are present,
output frequency available.
3 - Error Signal
Message is displayed via the parameter
Current
error
259
or
Warnings
269.
4 - Setting Frequency
The
Stator frequency
210
is higher than the
parameterized
Setting frequency
510
5
- Reference Frequency
reached
The
Actual frequency
241
of the drive has
reached the
Internal reference frequency
228
.
6
- Reference Percentage
Reached
The
Actual percentage
230
has reached the
Ref-
erence percentage
229
.
7 - Ixt warning
The
Warning Limit Short-Term Ixt
405 or
Warn-
ing Limit Long-Term Ixt
406
has been reached.
8
- Warning
Heat sink temperature
Max. heat sink temperature T
K
of 80 °C minus
the
Warning Limit
Heat Sink Temp.
407
reached.
9
- Warning
Inside temperature
Max. inside temperature T
i
of 65 °C minus the
Warning Limit Inside Temp.
408 reached.
10 - Warning Motor Temperature
Warning behavior according to parameterized
Operation mode Motor temperature
570 at max.
motor temperature T
PTC
.
11 - Warning General
The message is displayed via parameter
Warn-
ings
269.
12
- Warning overtemperature
The selected limit values
Warning Limit
Heat
Sink Temp.
407
,
Warning limit Inside Temp.
408
or the maximum motor temperature has
been exceeded.
13 - Mains Failure
Failure of the mains voltage and power regula-
tion active according to
Operation Mode
670
for
the voltage controller.
14
- Warning Motor Protect.
Switch
Parameterized
Operation Mode
571
for the mo-
tor protection switch has triggered.
15 - Warning Current Limitation A controller or the
Operation Mode
573 of the
intelligent current limits limits the output current.
16
- Controller Current Limit.
Long Term Ixt
The overload reserve for 60 s has been used up
and the output current is being limited.
17
- Controller Current Limit.
Short Term Ixt
The overload reserve for 1 s has been used up
and the output current is being limited.
18 - Controller Current Limit. TK
Max. heat sink temperature TK reached, intelli-
gent current limits of
Operation mode
573 ac-
tive.
19
- Controller Current Limit.
Motor Temp.
Max. motor temperature reached, intelligent cur-
rent limits of
Operation Mode
573 active.
20 - Comparator 1
The comparison according to the selected
Op-
eration mode
Comparator
1
540 is true.
Operating Instructions ACU
09/08