4-5
4007ES Panel Programmer Manual (
579-1167
)
System Options
Table 4-3. Active Status Reminder System Options
Option
Description
Fire
Reminder
The Fire Reminder option programs the system to periodically sound the
piezo if an uncleared Alarm condition exists at the panel, thereby reminding
system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled
Enabled
is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Pri2
Reminder
The Pri2 Reminder option programs the system to periodically sound the
piezo if an uncleared Priority 2 Alarm (security) condition exists at the panel,
thereby reminding system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled
Enabled
is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Supv
Reminder
The Supv Reminder option programs the system to periodically sound the
piezo if an uncleared supervisory condition exists at the panel, thereby
reminding system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled
Enabled
is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Trbl
Reminder
The Trbl Reminder option programs the system to periodically sound the piezo
if an uncleared Trouble condition exists at the panel, thereby reminding
system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled
Enabled
is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Local
Annunciation
If there is a per point serial DACT in the system, this setting specifies whether
the piezo on the local panel will sound. This option is useful in situations
where the panel is located in a public area (such as a lobby) and the occupant
does not want the piezo repeatedly sounding.
Panel Information and Configuration,
Continued
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......