13-11
4007ES Panel Programmer Manual (
579-1167)
Adding or Editing Network Information,
Continued
Programming
Distributed
Network Reset
5. Click on the
List
tab at the top of the programmer. When the
List
window appears, click on
the
General List
subtab at the bottom of the window. Scroll through the list, right click on
L105 and select
Tag List
.
6. Click on the
Filter
icon at the top of the
Tag List
. When the list of choices appears, click on
the
Network Externals
check box. All of the External Points appear.
7. Click on every entry for
P212
and press the space bar to add the entry to
L106
.
8. Repeat Steps 3 through 7 for every node on the network.
Distributed
Configuration
The digital pseudo points P463 and P464 are used to raise a trouble when a CO sensor is within
6 or 12 month of its expiration date. A transition from off to on of the digital pseudo point will
trigger a check on all CO sensors within the local panel. On site, where multiple panels are
linked together over the network, it is possible to synchronize the 2 digital pseudo points on
every node. To do so, the remote node must declare the local node’s P463 as External, since
P463 and P464 are always public by default. Once P463 is imported to the remote node’s job,
its L170 is automatically updated to include the imported digital pseudo point. The same
applies to P464 and L171. So when the remote node P463 is turned on, default SMPL equation
0-164 will turn the local node’s P463 to on. To declare an external point, refer to the section
“Procedure to Declare External Points” in this chapter.
Figure 13-12. Distributed Configuration
1. Open the network job by using the network programmer.
2. Open the job for the node that will serve as the central reset node.
3. When the ES Panel programmer appears, click the
Network
tab at the top of the
programmer.
4. When the Network window appears, click the
Network Points
subtab at the bottom of the
Network window.
5. Right click in the Network window.
6. When the choices appear, click on
Edit Externals
. A dialog box appears.
7. Click on the drop-down list box and choose one of the nodes on the network.
8. Click on
OK
to close the dialog. A tag list containing the public points from the selected
node appears.
9. Click on
P463
and press the space bar to select the point.
10. Click on
P464
and press the spacebar to select the point.
11. Click
OK
to close the taglist.
12. Repeat Steps 5 to 11 for every node on the network.
Node 4
L170
1:P463
2:P463
3:P463
L171
1:P464
2:P464
3:P464
Node 1
L170
2:P463
3:P463
4:P463
L171
2:P464
3:P464
4:P464
Node 2
L170
1:P463
3:P463
4:P463
L171
1:P464
3:P464
4:P464
Node 3
L170
1:P463
2:P463
4:P463
L171
1:P464
2:P464
4:P464
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......