9-32
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Step 5. Specifying
Hazard Area
Points
Each button accesses a tag list, with this you can select (tag) the specific points to associate
with the hazard. Follow these steps to tag points:
1. Click on the button corresponding to the type of suppression points you want to select. The
TagList
screen shown in Figure 9-35 appears.
2. The
TagList
screen displays all points with the relevant suppression release point type. To
select a specific point for inclusion in the hazard area being programmed, click on the point
to highlight it and then press the space bar.
Figure 9-35. Tagging Points
3. Click
OK
when you are finished selecting points. The screen containing the Tag List buttons
(Figure 9-34) reappears. Click
Next
when all points associated with this hazard area have
been chosen.
Continued on next page