8-9
4007ES Panel Programmer Manual (
579-1167)
Viewing, Adding, and Editing Lists,
Continued
Elevator Recall
List
The Elevator Recall list is made up of five groups, each corresponding to an elevator shaft
numbered from one to five. Each shaft group contains three lists - one for the primary recall
points, one for the alternate recall points, and one for the shutdown points.
The Elevator Shaft 1 group initially contains all of the system's monitor points and all relays
with the following point types - PRIMARY, ALTERN, and SHAFT (shutdown).
Figure 8-5. Elevator Recall Tab
Moving Between Points:
Follow these steps to move points from Elevator Shaft 1 group (where they are initially placed)
into other elevator shaft groups. Signal/relay points and monitor points can exist in multiple
groups at the same time.
1. Open the List Window by selecting the List Tab at the top of the Programmer.
2. Click on the Elevator Recall tab at the bottom of the List Window.
3. Select the monitor points to move:
a.
Right click on the Elevator Shaft group into which you want to move monitor points
(for example, using Figure 8-5, right click on the line called LST ELEVATOR
SHAFT
X
PRIMARY MONITOR ZONES). When the list of options appears, select
Tag List.
b.
In the Tag List, use the mouse or arrow keys to highlight each monitor point you want
to move into the group. Press the spacebar to tag or un-tag points to be added or
deleted. A point is selected when a “>>” symbol appears to the left of the point.
c.
Repeat these steps to move other monitor points into the group.
d.
Points that you move from Elevator Shaft 1 Primary Monitor Zones list to another
group are not automatically deleted from Elevator Shaft 1 Primary Monitor Zones list.
To delete points from this list, you need to highlight the Elevator Shaft 1 Primary
Monitor Zones list, press F9 to see the tag list, and then highlight the point you want to
delete and hit the space bar.
4. Select the signal/relay points to move as follows:
a.
Right click on the Elevator Shaft group into which you want to move the signal/relay
points (for example, using Figure 8-5, right-click on the line called LST ELEVATOR
SHAFT
X
PRIMARY RELAY). When the list of options appears, select Tag List. When
the list of options appears, select Tag List.
b.
In the Tag List, use the mouse or arrow keys to highlight each signal/relay point you
want to move into the group. Press the space bar to tag or un-tag points to be added or
deleted. A point is selected when a “>>” symbol appears to the left of the point.
c.
Repeat these steps for the Alternate and Shaft lists within the selected group.
d.
If you want to delete relay points from the Elevator Shaft 1 Primary Relay list, you
need to first right click on the Elevator Shaft 1 Primary Relay list, select Properties,
and set the AutoGen field to No. Next, press F9 to see the tag list, and then highlight
the point you want to delete and hit the space bar.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......