9-23
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Suppression
Release Use
Cases
Initial data window
• Program#: 3.
Note:
It is always 3 for a 4007ES FACP.
• Check
Enhanced Power Supply
because we have an IDNAC channel.
• Check
Cross Zone (Dual Detector)
.
• Set
First Stage Audible Notification
to Temporal.
Note:
The other options are Slow March Time (March20) and Fast March Time (March120). Fast
March Time should not be used because the Second Stage Audible Notification is fixed at
Fast March Time.
Timer Configurations
• Set
Manual Release
at 30 seconds and check the box.
• Set
Detector Release Delay
at 60 seconds and check box.
Hazard Area Lists window
• Press
Manual Release Points
and select the manual release point at
M1-11-0
.
• Press
Automatic Release Points
and select
Automatic Release Points at M1-18-0
and M1-19-0.
• Press
Abort Switches
and select
Abort Point at address M1-35.
• Press
Release Warning Points
and select
SIG914
.
• Press
Suppression Dump Points
and select
SIG3
and
M1-36-0.
• Press
Release Notification Audible NACs
and select
SIG913.
Use Case #1: 10 Second Delay Abort
Specific Configuration
Abort Logic Window
• Set
System Release after GREATER of Remaining Time Delay or 10 seconds
.
Table 9-3 describes actions and their corresponding responses.
Table 9-3. 10 Second Delay Abort, Actions and Responses
Action
Response
First detector is triggered.
RELSIG turns on at low cadence (Temporal).
RELWVIS turns on.
Manual device or second detector is triggered.
RELSIG turns on at high cadence (March120).
RELWVIS stays on.
Abort switch is pressed and maintained for
approximately 60 seconds after the RELSIG is in
high cadence.
While the abort switch is pressed the RELSIG stays
in high cadence and RELWVIS stays on.
Release the Abort Switch
RELSIG stays on in high cadence. RELWVIS stays
on for 10 seconds or for the remainder of the
automatic release timer, whichever is greater. When
the timer expires RELSIG and SUPRELS turn on
steady and RELWVIS remains on.
Continued on next page
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......