6-4
4007ES Panel Programmer Manual (
579-1167)
Editing Standard Component Properties,
Continued
Editing the Color
User Interface
To edit the Point Editing tab (Figure 6-4):
For each control key:
1. Select a switch mode
from the drop-down
list.
2. Enter a reference
address. Press F9 to
access the TagList
window.
3. Edit the point’s
custom label if
required. This label
should make the
point easily
identifiable.
4. Check the Invert
Pushbutton State box
to switch down the
point.
Figure 6-4. Color User Interface - Point Editing Tab
The following fields in the tab are filled by the programmer and cannot be edited:
• Reference Label
• Point
• Point Type
For each LED:
1. Select the appropriate mode from the drop-down list.
2. Enter a reference address.
Note:
Depending on the switch mode, a LED can be associated to a control key. To do so, the reference
address of the LED must be the same as the reference address of the control key.
3. Select the appropriate point type from the drop-down list.
a.
The default point type for the first two LED points are LEDRED
b.
The default point type for the third LED point is LEDGREEN
4. Edit the point’s custom label if required. This label should make the point easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Reference Label
• Point
• Invert Pushbutton State (grayed out)
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......