2-5
4007ES Panel Programmer Manual (
579-1167)
User Interface,
Continued
Tabs and Sub-
Tabs
Each tab represents a specific component or feature of the job that must be configured. The
tabs are placed in sequential order and should be completed in that order. Certain tabs are made
up of multiple sub-tabs that are found at the bottom of the page. All sub-tabs must be opened
and configured to complete the job.
Status bar
The Status bar is found at the bottom of the Programmer window and indicates the:
• Programmer status
• Time
Table 2-10. Tab list
Icon
Name
Sub-Tabs
Allows the user to:
Panel
• General Info
Enter and view the general panel and branch
information.
• System Options
Set the system options for the job.
• Access Levels
View the default user levels for specific tasks. Right
click on the user level to view and edit its properties.
• Passcode
Assignments
View and edit the passcode assigned to each user
level.
• Features
Enable or disable certain features with specific
dongles and codes.
Hardware
• Tree View
Display the panel components in a branch structure.
• Grid View
Display the panel components in a grid structure.
Point
-NA-
Display the list of all the points in the FACP.
Double click on any of the points to view and edit
their properties.
List
• General list
View all the Panel lists.
• Latching Supervisory
Verification
View and edit the items on the Latching Supervisory
Verification list.
• Alarm Verification
View and edit the items on Alarm Verification list.
• WALKTEST
View and edit the items on the WALKTEST list.
• Elevator Recall
View and edit the items on the Elevator Recall list.
Custom Control
• Custom Control
Create custom control equations which allow
operations to be customized per job.
• Floor Above/Floor
Below Wizard
Control the areas in which the NACs are activated.
• Selective Signaling
Wizard
Control the NACs that are activated.
• Sounder/Relay Base
Operation Wizard
Customize the default operation of select smoke
detectors
TrueAlert Zone
-NA-
View the points in each TrueAlert zone.
Port Vectoring
-NA
Assign certain cards to specific groups of events.
AMON Point Type
-NA-
View the analog monitor (AMON) points.
Zone Lists
-NA-
View the lists sorted by zone.
Network
• Network Information
• Network Points
Add and edit the lists of public and external points.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......