Releasing Specific Controls and Indications,
Continued
Releasing Service
Signal Silence
Programming -
Optional
(Pushbutton and
Yellow LED)
4. Disable the
Suppression Release Wizard
to delete the default equation written by the
Suppression Release Wizard
to silence the NACs on system silence. If it is not deleted it
will still silence the hazard area.
a.
Right click the wizard for that hazard and select
enable Manual Edit.
b.
Click
Yes
in the confirmation box that follows.
c.
Return to your custom control equations and find the equation that the
Suppression Release
Wizard l
abeled
On System Silence -
yourhazardname
d.
Right click and select
Delete
.