7-12
4007ES Panel Programmer Manual (
579-1167)
Point Editing for TrueAlert Device,
Continued
TrueAlert ES AV-L
Appliance Point
Editing
Table 7-8. TrueAlert ES AV-L Appliance Point Editing,
Continued
Option
Description
Coding Type
Select the Coding Type to set the cadence of the audible signal.
System Default
This sets the coding to the value determined in the System
Option tab.
Temporal
A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three
pulse group is separated by 1 ½ seconds of silence. Pattern
repeats until alarm silence.
March 20
A coded signal that uses 20 beats per minute. Each beat
consists of 1 ½ second pulse on, 1 ½ second off. Pattern
repeats until alarm silence.
March 60
A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120
A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady
On steadily.
Temporal 4
A CO gas warning that is a repeated sequence of four cycles
of 100 msec on with 100 msec off, followed by 5 seconds off.
Volume
Set the appliance volume:
High
To use this option the appliance's configuration control must
be set to Panel.
Low
To use this option the appliance's configuration control must
be set to Panel.
Hardware
Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
Note:
The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......