6-12
4007ES Panel Programmer Manual (
579-1167)
Editing Standard Component Properties,
Continued
Editing the Zone/
Relay Card
Auto Fill Window (Figure 6-18)
The auto fill function allows you to fill up the information for one point and then use this
information to automatically fill the information for the other points. To invoke this function,
select a point in the Point Editing tab grid and press F4. The Auto Fill window appears.
The following fields in the Auto Fill window are pre-filled with the values from the highlighted
point (from the Point Editing tab):
• All
• Point Forward
• Selected
1. Select to which point you want to apply the auto fill from the Auto Fill drop-down menu.
The choices are:
• All (programmer changes all the points on the card to match the auto fill selection)
• Point Forward (programmer changes the highlighted point and all subsequent points on
the card to match the auto fill selection)
• Selected (programmer changes the highlighted point to match the auto fill selection)
2. To apply the same
custom label to other
points, check the
Custom Label check
box.
3. To add an
identification number
after the label, check
the Automatically
increment last number
in custom labels check
box.
4. The following fields
are grayed out:
• Reference
Address
• Coding Type
• Candela Rating
• Mode
Figure 6-18. Zone / Relay Point Editing - Auto Fill Window
5. Click on
OK
to confirm the edits.
Note:
If the point selected is a MONA, the Auto Fill affects only the primary points (1, 3, 5, or 7) for the
custom label since the second points (2, 4, 6, or 8) are reserved. However, if the Alt Custom Label is
checked, both the first and the second point of a MONA are affected.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......