13-4
4007ES Panel Programmer Manual (
579-1167)
Adding or Editing Network Information,
Continued
Editing the
Network Name
and Node Number
The Network Information tab includes the following fields. Use the guidelines outlined in the
table when setting these fields.
Field
Guidelines
Advanced
Network
Information
Network
Click on the Advanced button and use the dialog that appears to change the network
to which the 4007ES panel is assigned.
Node
Click on the Advanced button and use the dialog that appears to change the node
number of the 4007ES panel.
Master
Timekeeper
Select to use this panel as the network’s master timekeeper. Only one master
timekeeper per network.
Annunciate
Common Troubles
Select if you wish to have other panel’s common trouble messages annunciated on
this panel.
Annunciate Network
Troubles
Select if you wish to have this panel’s Network messages sent to the system’s
annunciators.
Annunciate Extra
Node Troubles
The Annunciate Extra Node Option prevents a node from annunciating an Extra
Node Trouble following the addition of a new node. Guidelines for setting this option
are as follows:
• Unselect this option on nodes without a need to annunciate events from the new
node.
• Select this option on the node that functions as the network's central annunciator.
Auto Gen List
Externals
When selected, this option adds the external points from other nodes to the system
lists on this node. When it does this, it adds the points to the list based on the point
type of the point.
Miscellaneous
Network
Information
Network Prefix
Enter descriptive text in this field. This text appears when the more info. field is
selected on a TSW.
Special Analog
Initialization
Checking this option prevents analog detectors from sending status on initialization if
the value is not an alarm or trouble condition. However, if the analog value indicates
an alarm or trouble condition exists, the detector will send its state.
If you select this option and you have Custom Control equations that contain the
Compare Opcode and Current Value qualifier, be aware that the equation will not
trigger on network initialization, but will trigger on subsequent value changes. Also, if
analog detectors have a numeric value on a GCC screen, the screen will not update
until the point's value changes after network initialization.
Note: To avoid Network Initialization troubles, all network nodes must be set the same
way.
Inhibit Priority-Only
EQBs
This option prevents network EQBs from being generated for status changes that
only affect priority and not the status of the point. For example, a Custom Control
equation triggers that modifies the priority of a public control point, putting the point to
the reset priority but not changing its state. If this option is selected, no EQB will be
generated. The side effect of choosing this option is that there will be a display
mismatch of the priority between the owner and the external node.
Note:
Select this option only if required to reduce network traffic.
Inhibit Sounder-
EQBs
This option prevents TrueAlarm sounder/relay base (non-combo points) from
generating network EQBs when only the status of the sounder/relay changes. If the
sounder/relay is turned on or off without a threshold or logical state change on the
sensor portion of the device, no EQB will be generated to external nodes. Status
changes to the device that involve a logical status change (e.g. alarm, trouble), or a
sensor threshold level change will still report.
Note:
Select this option only if required to reduce network traffic.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......