background image

 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 

 

 

 
 
 

 

 
 

   
 
 
 
 
 
 
 
 
 
 

Max.Hp 

For AC Motors

 

Max.  
Volt-  
age

 

Max. 

Continous  

Amp  

Rating

 

AC Volts

 

Single-
Phase

 

Poly- 
Phase

 

600 

45

 

115 
200 
230 

460/575 

 

7½ 

-

 

10 
15 
25

 

CAUTION

:

 

Before  installing  in  a  nuclear 

application, determine that the product is 
intended for such use.

 

WARNING:

 Disconnect power 

before In-stalling or servicing.

 

DESCRIPTION

  

A General Electric 300-Line full voltage 
magnetic combination starter consists of a 
magnetic contactor with a three leg block 
overload relay and a manually operated 
circuit breaker or disconnect switch. The 
disconnect switch may either be fusible or 
non-fusible. The non-fusible disconnect 
switch provides a means of manually 
disconnecting the motor from the line. The 
circuit breaker or fusible disconnect switch 
provides motor branch short-circuit 
protection. The overload relay provides, 
motor protection against running and 
stalled motor overload. 

The  overload  relay  is  provided  with  a 
yellow  trip  indicator  which  is  located  to 
the  right  of  the  reset  arm,  and  is  visible 
when  the  overload  relay  is  tripped. 
 

FEATURES  

    

1.

 Strongbox coil.  

2.

 Overload relay, incorporates a dial for 

±10% field adjustment of tripping current, 
so that it is no longer necessary to change 
heaters to eliminate such problems as 
nuisance tripping in hot weather.  

3.

 Overload trip indicator.  

4.

 Straight through wiring.  

5. 

Oversized power terminals will 

accommodate up to #4 wire.  

6.

 Starter can be disassembled and 

inspected in a matter of seconds.  

7.

Circuit breaker or disconnect switch is 

mechanically interlocked with the 
enclosure door to prevent opening the door 
until the handle is moved to the OFF 
position.

  

 

COIL REMOVAL

  

The encapsulated coil is impervious 
to moisture, dirt, and oil. It resists 
mechanical damage and failure due 
to high humidity. No tools are 
required to remove coil. 

1.

 Remove power from device.  

2.

 Press against coil while pulling up 

slightly on coil retainers (A—Figure 1 
or 2) and move retainers away from 
coil.  

3.

 Withdraw magnet assembly, coil, 

molded cover, and movable arm 
from device.  

4.

 Withdraw spring clip (B—Figure 1 

or 2) and remove armature from 
movable arm.  

5.

 Remove coil from magnet.  

6.

 Replace coil.  

7.

 Reassemble device by reversing 

procedure.

 

2.

 Clean magnet mating surfaces 

of any dust or foreign matter.  

3.

 Select heaters in accordance 

with heater table, which 
accompanies each device.  

4.

 Operate movable magnet and 

operating arm by pressing on the 
nameplate to assure free 
movement.  

5.

 Mount the starter on a sturdy 

vertical support.  

6.

 The overload relay may be reset 

manually by depressing and 
releasing the reset arm. Overload 
relays with an optional normally 
open contact are electrically 
isolated from the normally closed 
contact.

  

7.

 Provide motor branch circuit 

protection in accordance with the 
National Electrical Code.

  

 

CONTACT REMOVAL

  

Movable contacts can be inspected 
and replaced in seconds—without 
tools (Figure 3).

 

 

 

RATINGS 

INSTALLATION 

Before connecting the starter:  

1.

 Remove all packing. 

 

These instructions do not purport to cover all details or variations in equipment not to provide for every possible contingency to 
be met in connection with installation, operation or maintenance. Should further information be desired or should particular 
problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the GE Company.

 

Instructions for 
NEMA size 2

 

Combination  
Magnetic Starters 

CR307-CR308, CR310-CR311, CR387, CR390, CR407-CR408 
CR410-CR415, CR487, CR490, CR492, CR494 Series

 

 

GEH-4776 Instruction 