Setpoint channel and closed-loop control
7.3 V/f control
Converter cabinet units
436
Operating Instructions, 07/2016, A5E03347396A
Figure 7-10 Slip compensation
Function diagram
FP 6310
Resonance damping and slip compensation
Parameters
•
r0330
Rated motor slip
•
p1334
Slip compensation start frequency
•
p1335
Slip compensation, scaling
p1335 = 0.0%: slip compensation is deactivated.
p1335 = 100.0%: slip is fully compensated.
•
p1336
Slip compensation limit value
•
r1337
CO: Actual slip compensation
•
p1351
CO: Motor holding brake start frequency