Electrical installation
4.10 Other connections
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
193
Table 4- 71 Terminal block -X2 – connection NAMUR control terminal block
Terminal
Designation
Default
Comment
10
DI
ON/OFF (dynamic)/
ON/OFF (static)
Effective operation can be coded by a wire jumper on
terminal -X400:9;10 (delivery condition: jumper insert-
ed):
jumper inserted: ON/OFF (dynamic)/
jumper removed: ON/OFF (static)
11
DI
OFF (dynamic)
12
DI
Faster
Motorized potentiometer
13
DI
Slower
Motorized potentiometer
14
DI
RESET
Acknowledge error
15
DI
Interlock
OFF2
16
DI
Counterclockwise
"0" signal: CW phase sequence
"1" signal: CCW phase sequence
17
DI
Power Disconnection
EMERGENCY OFF circuit
"0" signal: Power disconnection
"1" signal: No power disconnection
18
30
DO (COM)
Ready for operation
Relay output (NO contact)
31
DO (NO)
32
DO (COM)
Motor turning
Relay output (NO contact)
33
DO (NO)
34
DO (NO)
Fault
Relay output (two-way contact)
35
DO (COM)
36
DO (NC)
50/51
AI 0/4-20 mA
Speed setpoint
Default: 4 ... 20 mA
60/61
AO 0/4-20 mA
Motor frequency
Default: 4 ... 20 mA
(preallocated with motor frequency, can be reparame-
terized for other variables)
62/63
AO 0/4-20 mA
Motor current
Default: 4 ... 20 mA
(preallocated with motor current, can be reparameter-
ized for other variables)
Max. connectable cross-section: 2.5 mm²
Table 4- 72 Terminal block -X3 – connection for the motor PTC thermistor sensor
Terminal
Designation
Default
Comment
90/91
AI
Connection for a PTC ther-
mistor
Shutdown if limit value is exceeded.
Max. connectable cross-section: 2.5 mm²
Adapting the analog inputs and outputs
If the setting ranges of the analog inputs and outputs are to be changed, the associated
interface converters (-T401 / -T402 / -T403) must be set. The corresponding interface
converter must be removed for this purpose and the rotary switch on the side ("S1") turned
to the corresponding position.
Summary of Contents for SINAMICS G150
Page 1: ......
Page 2: ......
Page 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Page 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Page 679: ......
Page 680: ......