Device overview
2.4 Wiring principle
Converter cabinet units
32
Operating Instructions, 07/2016, A5E03347396A
①
The line infeed can be either 6-pulse or 12-pulse.
②
Up to a rated power of 2400 kW, motors can be connected to a single winding system or
to a double winding system. Up to a rated power of 2700 kW, motors can be connected to a
single winding system or to a triple winding system.
Note
Motors with multiple winding systems
Motors with multiple winding systems can also be operated as a single winding system by
connecting the motor windings in parallel at the terminal box and setting the parameter
p7003 during commissioning.
→ See "Commissioning"
Note
PE connection of the motor
The PE connection at the motor must be fed back directly to the cabinet unit.