Functions, monitoring, and protective functions
9.2 Drive functions
Converter cabinet units
524
Operating Instructions, 07/2016, A5E03347396A
Notes on setting the release (opening) time (p1216):
●
The release time (p1216) should be set longer than the actual release time of the holding
brake. As a result, the drive will not accelerate when the brake is closed.
Notes on setting the closing time (p1217):
●
The closing time (p1217) should be set longer than the actual closing time of the holding
brake. As a result, the pulses are suppressed only after the holding brake is closed.
●
If the closing time (p1217) is set too low compared to the actual closing time of the
holding brake, the load may drop suddenly.
●
If the closing time (p1217) is set too high compared to the actual closing time of the
holding brake, the controller acts against the holding brake and thus reduces its service
life.
Function diagram
FP 2701
Simple brake control (r0108.14 = 0)
Parameter
•
r0056.4
Magnetizing completed
•
r0060
CO: Speed setpoint before the setpoint filter
•
r0063[0...2] CO: Actual speed value
•
r0108.14
Extended brake control
•
p0855[C]
BI: Unconditionally release holding brake
•
p0856
BI: Speed controller enabled
•
p0858
BI: Unconditionally apply holding brake
•
r0899.12
BO: Holding brake open
•
r0899.13
BO: Command, close holding brake
•
p1215
Motor holding brake configuration
•
p1216
Motor holding brake release time
•
p1217
Motor holding brake closing time
•
p1226
Threshold for standstill detection
•
p1227
Standstill detection monitoring time
•
p1228
Pulse suppression delay time
•
p1278
Brake control diagnostic evaluation