Electrical installation
4.10 Other connections
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
119
4.10.1
dv/dt filter compact plus Voltage Peak Limiter (Option L07)
Description
The dv/dt filter compact plus Voltage Peak Limiter comprises two components: the dv/dt
reactor and the voltage-limiting network (Voltage Peak Limiter), which cuts off the voltage
peaks and feeds back the energy into the DC link. The dv/dt filter compact plus Voltage Peak
Limiter is designed for motors for which the voltage strength of the insulation system is
unknown or insufficient.
dv/dt filters compact plus Voltage Peak Limiters limit the voltage rate of rise dv/dt to values <
1600 V/µs - and the typical voltage peaks to the following values according to limit value
curve A acc. to IEC 60034-25:2007:
●
< 1400 V at 660 V < U
line
< 690 V.
Restrictions
The following constraints should be noted when a dv/dt filter compact plus Voltage Peak
Limiter is deployed:
●
The output frequency is limited to no more than 150 Hz.
●
Maximum permissible motor cable lengths:
–
Shielded cable: max. 100 m
–
Unshielded cable: max. 150 m
NOTICE
Damage to the dv/dt filter compact by exceeding the maximum output frequency
The maximum permissible output frequency when a dv/dt filter compact is used is 150 Hz.
The dv/dt filter compact can be damaged if the output frequency is exceeded.
•
Operate the dv/dt filter compact with a maximum output frequency of 150 Hz.
NOTICE
Damage to the dv/dt filter compact during continuous operation with low output frequencies
Uninterrupted duty at an output frequency less than 10 Hz can result in thermal overload
and destroy the dv/dt filter.
•
When using a dv/dt filter compact plus voltage peak limiter do not operate the drive
continuously with an output frequency less than 10 Hz.
•
You may operate the drive for a maximum load duration of 5 minutes at an output
frequency less than 10 Hz, provided that you then select an operation with an output
frequency higher than 10 Hz for a period of 5 minutes.