Commissioning
5.3 Procedure for commissioning with STARTER
Converter cabinet units
238
Operating Instructions, 07/2016, A5E03347396A
Note
Naming devices
ST (Structured Text) conventions must be satisfied for the name assignment of IO
devices in Ethernet (SINAMICS components). The names must be unique within
Ethernet.
Rules for assigning names:
•
Other than "-" and ".", no special characters (such as accented characters, spaces,
brackets) are permitted in the name of an IO device.
•
The device name must not begin or end with the "-" character.
•
The device name must not begin with a number.
•
Maximum total length of 240 characters (lowercase characters, numbers, hyphen, or
period).
•
A name component within the device name, e.g. a string between two periods, must
not exceed 63 characters.
•
The device name must not take the form n.n.n.n (n = 0, ... 999).
•
The device name must not begin with the character sequence "port-xyz" or "port-xyz-
abcde" (a, b, c, d, e, x, y, z = 0, ... 9).
Figure 5-36 Edit Ethernet Node
9.
Pressing the "Update (F5)" button displays the IP address and name in the entry for the
bus node. If not, close the "Accessible nodes" screen and perform another search for
accessible nodes.
10.If the Ethernet interface is displayed as bus node, select the entry and click the "Accept"
button.