Operation
6.11 Communication via EtherNet/IP
Converter cabinet units
394
Operating Instructions, 07/2016, A5E03347396A
No. Service
Type
Name
Value/explanation
UINT32 Frame Too Long
Structure too large
UINT32 MAC Receive
Errors
Transmission unsuccessful as a result of an inter-
nal MAC sublayer receive error.
6
get, set Struct of Interface Control
UINT16 Control Bits
UINT16 Forced Interface
Speed
10
get
String
Interface_Label
Interface-Label
Parameter Object, Instance Number: 401 hex
Supported services
Class
•
Get Attribute all
Instance
•
Get Attribute all
•
Set Attribute single
Table 6- 52 Class Attribute
No. Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Parameter access to drive object 0 (DO 0) is realized via this class.
Example: Read parameter 2050[10] (connector output to interconnect the PZD received from
the fieldbus controller)
Get Attribute single function with the following values:
●
Class = 401 hex
●
Instance = 2050 = 802 hex
≙
parameter number
●
Attribute = 10 = A hex ≙ Index 10
Example: Parameter 1520[0] writing (upper torque limit)
Set Attribute single function with the following values:
●
Class = 401 hex
●
Instance = 1520 = 5F0 hex ≙ parameter number
●
Attribute = 0 = 0 hex ≙ index
0
●
Data = 500.0 (value)