Operation
6.12 Communication via MODBUS TCP
Converter cabinet units
404
Operating Instructions, 07/2016, A5E03347396A
Structure of a read request via Modbus function code 03 (FC 03)
Any valid register address is permitted as the start address.
Via FC 03, the control can address more than one register with one request. The number of
addressed registers is contained in bytes 10 and 11 of the read request.
Table 6- 58 Structure of a read request via slave number 17, example
Value
Byte Description
MBAP header
03 h
00 h
6D h
00 h
02 h
7
8
9
10
11
Register start address "High" (register 40110)
Register start address "Low"
Number of registers "High" (2 registers: 40110; 40111)
number of registers "Low"
The response returns the corresponding data set:
Table 6- 59 Slave response to the read request, example
Value
Byte Description
MBAP header
03 h
04 h
11 h
22 h
33 h
44 h
7
8
9
10
11
12
Number of bytes (4 bytes are returned)
Data first register "High"
Data first register "Low"
Data second register "High"
Data second register "Low"
Table 6- 60 Invalid read request
Read request
Inverter response
Invalid register address
Exception code 02 (invalid data address)
Read a write-only register
Telegram in which all values are set to 0.
Read a reserved register
Controller addresses more than 125 registers
Exception code 03 (invalid data value)
The start address and the number of registers of
an address are located outside of a defined regis-
ter block
Exception code 02 (invalid data address)