Operation
6.6 Control via the operator panel
Converter cabinet units
312
Operating Instructions, 07/2016, A5E03347396A
Access level (factory setting: Expert):
The different parameters required for this complex application are filtered so that they can be
displayed as clearly as possible. You select them according to the access level.
An expert level, which must only be used by expert personnel, is required for certain actions.
Note
Copy from RAM to ROM
When the operator input inhibit or parameterization inhibit is activated, a "Copy from RAM to
ROM" is automatically executed to back the parameter settings up in non-volatile memory on
the memory card.
6.6.8
Faults and alarms
Indicating faults and alarms
If a fault occurs, the drive displays the fault and/or alarm on the operator panel. Faults are
indicated by the red "FAULT" LED and a fault screen is automatically displayed. You can use
the F1 Help function to call up information about the cause of the fault and how to remedy it.
You can use F5 Ack. to acknowledge a stored fault.
Alarms are indicated by means of the yellow "ALARM" LED. The system also displays a note
in the status bar providing information on the cause.
What is a fault?
A fault is a message from the drive indicating an error or other exceptional (unwanted) status
that causes the drive to shutdown. This could be caused by a fault within the converter or an
external fault triggered, for example, by the winding temperature monitor for the motor. The
faults are displayed and can be reported to a higher-level control system via PROFIBUS. In
the factory default setting, the message "converter fault" is also sent to a relay output. Once
you have rectified the cause of the fault, you have to acknowledge the fault message.
What is an alarm?
An alarm is the response to a fault condition identified by the drive. It does not result in the
drive being switched off and does not have to be acknowledged. Alarms are "self
acknowledging", that is, they are reset automatically when the cause of the alarm has been
eliminated.