3. Press the "Safe basic functions" button:
A
$
%
&
Set the following:
– (A) Set the monitoring time to the maximum value (9000 hours). This means that the
forced checking procedure monitoring for the basic functions is deactivated.
– This monitoring is not required when using the extended functions, as the forced
checking procedure for the extended functions also includes the forced checking
procedure for the basic functions.
– (B) Setting not required.
– (C) If required, interconnected the status of the STO function, e.g. with a digital output
of your choice.
4. Close the screen form.
You have set the forced checking procedure (test stop) of the extended functions.
Commissioning
5.12 Setting extended functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2