17.Press the "Start safety commissioning" button.
18.Enter the password for the safety functions.
19.Confirm the prompt for saving your settings (copy RAM to ROM).
20.Disconnect the online connection.
21.Switch off the inverter supply voltage.
22.Wait until all LEDs on the inverter go dark.
23.Switch on the inverter supply voltage again.
24.Perform a reduced acceptance test.
Reduced acceptance after a component has been replaced and a firmware change
You have replaced the Control Unit and transferred the safety function settings from the PC
to the new Control Unit.
Replacing the Control Unit with data backup in the operator Panel
Precondition
You have backed up the actual settings of the Control Unit to be replaced to an operator panel.
Procedure
To replace the Control Unit, proceed as follows:
1. Switch off the inverter power supply voltage.
2. Remove all cables from the inverter.
3. After 5 minutes, check whether the device is in a no-voltage condition.
4. Release the four Power Modules screws.
5. Remove the Power Module.
6. Withdraw the ribbon cable to the CPI module from the Control Unit.
7. Release the four screws from the Control Unit.
8. Remove the defective Control Unit.
9. Mount the new Control Unit. The new Control Unit must have the same article number and
the same or higher firmware version as the Control Unit that was replaced.
10.Insert the ribbon cable to the CPI module back into the Control Unit.
11.Mount the Power Module on the Control Unit.
12.Reconnect all of the cables to the inverter.
13.Switch on the power supply voltages again.
14.Connect the handheld operator panel to the inverter.
15.Transfer the settings from the Operator Panel to the inverter.
16.Wait until the transfer is complete.
Corrective maintenance
7.5 Replacing components of the SINAMICS G110M inverters
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2