Procedure with Startdrive
To reset the safety function settings to the factory setting without changing the standard
settings, proceed as follows:
1. Go online.
2. Select "Commissioning".
3. Select "Backing up/reset".
4. Select "Safety parameters are reset".
5. Press the "Start" button.
6. Enter the password for the safety functions.
7. Confirm that the parameters have been saved (RAM to ROM).
8. Go offline.
9. Switch off the inverter supply voltage.
10.Wait until all LEDs on the inverter go dark.
11.Switch on the inverter supply voltage again.
You have restored the safety functions in the inverter to the factory settings.
Exception: The password for the safety functions is not reset.
Resetting the password for the safety functions (Page 109)
Parameter Description
p0010
Drive commissioning parameter filter
0
Ready
30
Parameter reset
p9761
SI password entry (factory setting: 0000 hex)
Permissible passwords lie in the range 1 … FFFF FFFF.
p9762
New SI password
p9763
Confirm SI password
Confirm the new Safety Integrated password.
Commissioning
5.6 Resetting the safety functions to the factory setting
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD