Carry out a forced checking procedure of the basic functions
Preconditions
● STO is not active.
● The motor is switched on (ON/OFF1 = 1), and is at a standstill (speed setpoint = 0).
Procedure
To start the forced checking procedure, proceed as follows:
1. Select the STO function.
2. The inverter checks its safety-related circuits. This check takes several milliseconds.
3. Deselect the STO function.
4. Check that alarm A01699 is no longer present.
You have performed the forced checking procedure.
Carry out the forced checking procedure of the "STO via Power Module terminals" function
Requirements
● STO is not active.
● The motor is switched on (ON/OFF1 = 1), and is at a standstill (speed setpoint = 0).
Procedure
To start the forced checking procedure, proceed as follows:
1. Select the "STO via Power Module terminals" function.
2. The inverter checks its safety-related circuits. This check takes several milliseconds.
3. Deselect the "STO via Power Module terminals" function.
4. Check that alarm A01678 is no longer active.
You have performed the forced checking procedure.
Operation
6.2 Regularly testing the safety functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD