Procedure with STARTER
Enable the safety functions.
Procedure with Startdrive
Proceed as follows to enable the safety functions:
1. Select "Control type/safety
functions".
2. Enable safety functions
STO … SSM.
You must always set these safety
functions, even if you only use the
SDI function.
3. If you are using the SDI function,
then enable SDI.
You have enabled the safety functions in the inverter.
Parameter
Description
p9501
Enable safety functions
.00
1 signal: Enable the extended functions (without SDI)
.17
1 signal: Enable SDI
Commissioning
5.12 Setting extended functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
146