You have reset the password for the safety functions.
Parameter
Description
p0010 = 95
Drive commissioning parameter filter
Safety Integrated commissioning
p9761
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 … FFFF FFFF.
p9762
New password
p9763
Confirm password
p9701 = DC
hex
Confirm data change (factory setting: 0)
Confirm the SI basic parameter change.
p0010 = 0
Drive commissioning parameter filter
0: Ready
p0971 = 1
Save parameter
1: Save the drive object (copy from RAM to ROM)
After the inverter has saved the parameters in a non-volatile fashion, then p0971 = 0.
Commissioning
5.7 Resetting the password for the safety functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
111