Parameter
Description
p0010 = 95
Drive commissioning parameter filter
Safety Integrated commissioning
p9601
Enable functions integrated in the drive (factory setting: 0000 bin)
Functions that have been
enabled:
Functions that have been enabled:
0 hex
None
80 hex
STO via Power Module terminals
1 hex
Basic functions via on‐
board terminals
81 hex
● Basic functions via onboard terminals
● STO via Power Module terminals
4 hex
Extended functions via
onboard terminals
84 hex
● Extended functions via onboard
terminals
● STO via Power Module terminals
8 hex
Basic functions via PRO‐
FIsafe
88 hex
● Basic functions via PROFIsafe
● STO via Power Module terminals
9 hex
● Basic functions via
PROFIsafe
● Basic functions via
onboard terminal
89 hex
● Basic functions via PROFIsafe
● Basic functions via onboard terminals
● STO via Power Module terminals
C hex Extended functions via
PROFIsafe
8C hex ● Extended functions via PROFIsafe
● STO via Power Module terminals
D hex ● Extended functions
via PROFIsafe
● Basic functions via
onboard terminals
8D hex ● Extended functions via PROFIsafe
● Basic functions via onboard terminals
● STO via Power Module terminals
p9761
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 … FFFF FFFF.
p9762
New password
p9763
Confirm password
Commissioning
5.9 Configuring safety functions and PROFIsafe using STARTER
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
115