Setup
3.4 Inputs and outputs
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
81
3.4.4.2
Change operation mode
Description
Sets operation mode.
Setting Off; Frequency output; Pulse output
Default Off
Related
Path
Setup
→
Inputs and outputs
→
Channel 4 - input/output
→
Change operation mode
3.4.4.3
Frequency output
3.4.3.3.1 Process value
Description
Select process value for the frequency output.
Setting Volume flow; Mass flow; Flow velocity; Sound velocity; Density; Kinematic viscosity; Medi-
um temperature
Default Volume flow
Related
Path
Setup
→
Inputs and outputs
→
Channel 4 - input/output (4)
→
Frequency output
→
Process
value
3.4.3.3.2 Direction
Description
Flow direction filter applicable for process values mass flow/volume flow/flow
velocity/standard volume flow rate (only hydrocarbon and gas applications).
Setting Positive; Negative; Bidirectional; Bidirectional (symmetric)
Default Positive
Related
Path
Setup
→
Inputs and outputs
→
Channel 4 - input/output
→
Frequency output
→
Direction