3.1 Sensor settings
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
21
Setting 200.0 m/s to 4000.0 m/s
Default 3000.0 m/s
Related
Path
Setup
→
Sensor settings
→
Pipe settings
→
Wall sound velocity
3.1.3.7
Liner settings
3.1.3.7.1 Liner thickness
Description
Pipe liner thickness
Setting 0.0 m to 0.5 m
Default 0.0 m
Related
Path
Setup
→
Sensor settings
→
Pipe settings
→
Liner settings
→
Liner thickness
3.1.3.7.2 Liner material
Description
Liner material - Read only. Can only be changed via the Sensor Wizard.
Setting Read only: Custom; Cement; Coal tar; Enamel; Glass; Plastic; Hi_dens_Poly; PTFE; Rub-
ber
Default Custom
Related
Path
Setup
→
Sensor settings
→
Pipe settings
→
Liner settings
→
Liner material
3.1.3.7.3 Liner sound velocity
Description
Liner material sound velocity (clamp-on).
Setting 200.0 m/s to 4000.0 m/s
Default 2000.0 m/s