Setup
3.4 Inputs and outputs
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
65
Positive flow across zero with positive scaling
①
Lower range value
②
Low flow cut-off
③
Upper range value
④
Upper saturation limit
⑤
Lower saturation limit
⑥
Lower fault current
⑦
Span
Current output setting
●
Process value = Mass flow
●
Direction = Bidirectional
●
Loop current scale = 4-20 mA NAMUR
●
Upper range value = 400 kg/h
●
Lower range value = -100 kg/h
●
Fail-safe behaviour = Upper fault current
●
Low flow cut-off = 25 kg/h