Setup
3.4 Inputs and outputs
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
73
Related
Path
Setup
→
Inputs and outputs
→
Channel 2 - output
→
Current output
→
Lower range value
3.4.3.4.6 Damping value
Description
Sets the Damping (filtering) to smooth out response to sudden changes in measurement.
An increase to Damping value increases response time of device, and affects digital value
and loop current. If output values are noisy, increase Damping value. For faster response
time, decrease Damping value. Find a value that meets requirements of signal stability and
response time.
Setting 0.00 s to 100.00 s
Default 0.00 s
Related
Path
Setup
→
Inputs and outputs
→
Channel 2 - output
→
Current output
→
Damping value
3.4.3.4.7 Fail-safe behaviour
Description
Current output reaction in case of a fault.
Setting Lower fault current; Upper fault current; Last valid value; Current value; Fail-safe value
Default Lower fault current
Related
Path
Setup
→
Inputs and outputs
→
Channel 2 - output
→
Current output
→
Fail-safe behaviour
3.4.3.4.8 Fail-safe value
Description
Output value in case of a fault and when fail-safe behaviour configured to fail-safe value.
Setting 0.0 mA to 25.0 mA
Default 0.0 mA
Related
Path
Setup
→
Inputs and outputs
→
Channel 2 - output
→
Current output
→
Fail-safe value
Summary of Contents for FST020
Page 2: ......
Page 122: ...Setup 3 14 Status icons FST020 Function manual 120 Function Manual 09 2017 A5E42949526 AA ...
Page 186: ...Security 6 9 Logout FST020 Function manual 184 Function Manual 09 2017 A5E42949526 AA ...
Page 188: ...Language 7 1 Language FST020 Function manual 186 Function Manual 09 2017 A5E42949526 AA ...
Page 192: ...Index FST020 Function manual 190 Function Manual 09 2017 A5E42949526 AA ...
Page 193: ......