Setup
3.1 Sensor settings
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
25
3.1.5.4
Kinematic viscosity
Description
Viscosity of media used for compensation.
Input during setup.
Setting 0.00 m²/s to 5000.0 m²/s
Default 0.000001 m²/s
Related
Path
Setup
→
Sensor settings
→
Medium characteristics
→
Kinematic viscosity
3.1.5.5
Process density
Description
Density of media used for compensation.
Input during setup.
Setting 0.0 kg/m³ to 2000.0 kg/m³
Default 1000.0 kg/m³
Related
Path
Setup
→
Sensor settings
→
Medium characteristics
→
Process density
3.1.6
Sensor selection
3.1.6.1
Sensor model
Description
Installed sensor model (for multi-path all must be the same). Read only. Can only be
changed via the Sensor Wizard. Indicates the Sensor model chosen from the sensor setup
wizard.
Setting Read only: FSS200 high precision; FSS200 / 1011 Universal; FSS200 / 991 high tempera-
ture; 1011 high precision liquid
Default FSS200 / 1011 Universal
Related
Path
Setup
→
Sensor settings
→
Sensor selection
→
Sensor model