Setup
3.4 Inputs and outputs
FST020 Function manual
64
Function Manual, 09/2017, A5E42949526-AA
Positive flow with negative scaling
①
Low flow cut-off
②
Upper range value
③
Maximum output current
④
Upper fault current
⑤
Lower range value
⑥
Lower saturation limit
⑦
Span
Current output setting
●
Process value = Mass flow
●
Direction = Positive
●
Loop current scale = 4-20 mA (maximum 25 mA)
●
Upper range value = 100 kg/h
●
Lower range value = 400 kg/h
●
Fail-safe behaviour = Upper fault current
●
Low flow cut-off = 25 kg/h