Setup
3.1 Sensor settings
FST020 Function manual
22
Function Manual, 09/2017, A5E42949526-AA
Related
Path
Setup
→
Sensor settings
→
Pipe settings
→
Liner settings
→
Liner sound velocity
3.1.3.8
Inner pipe roughness
Description
Roughness of inner pipe/liner material.
Setting 0.0 m to 0.01 m
Default 0.0001 m
Related
Path
Setup
→
Sensor settings
→
Pipe settings
→
Inner pipe roughness
3.1.3.9
Inner pipe diameter
Description
Read only. Calculated inner diameter of pipe (clamp-on).
Setting
Default 0.0 m
Related
Path
Setup
→
Sensor settings
→
Pipe settings
→
Inner pipe diameter
3.1.4
Upstream and downstream conditions
3.1.4.1
Disturbed flow profile compensation
Description
Disturbed flow profile compensation enable/disable
Setting Enable; Disabled
Default Disabled
Related
Path
Setup
→
Sensor settings
→
Upstream and downstream conditions
→
Disturbed flow profile
compensation