Description
Select units for displayed Totalizer 1. The set of units depends on the selected process
value. Units are not applied at communication interface.
Setting Process value = Mass flow: g (grams); kg (kilograms); t (1 t = 1000 kg); STon (1 STon =
2000 lb); T (1 T = 2240 lb); oz (ounces); lb (pounds); Process value = Volume flow: l (li-
ters); hl (hectoliters); m³ (cubic meters); gal (US gallons); i.gal (Imperial gallons); BBL31.5
(1 barrel = 31.5 US gallons); BBL31 (1 barrel = 31 US gallons); BBL42 (1 barrel = 42 US
gallons); in³ (cubic inches); ft³ (cubic feet); yd³ (cubic yards);bush (bushels); Process value
= Standard volume flow: Nl (normal liters); Nm³ (normal cubic meters); Sl (standard liters);
Sft³ (standard cubic feet); Sm³ (standard cubic meters); custom units (see Custom units /
Custom conversion factor)
Default kg (kilograms)
Related
Path
Setup
→
Totalizers
→
Totalizer 1
→
Units
3.3.1.3
Custom units
Description
User specific string to define custom unit Totalizer 1 values.
Setting -
Default -
Related
Path
Setup
→
Totalizers
→
Totalizer 1
→
Custom units
3.3.1.4
Custom conversion factor
Description
Conversion factor for user specific standard mass flow values related to SI kg.
Setting -
Default 1.0
Related
Path
Setup
→
Totalizers
→
Totalizer 1
→
Custom conversion factor
Summary of Contents for FST020
Page 2: ......
Page 122: ...Setup 3 14 Status icons FST020 Function manual 120 Function Manual 09 2017 A5E42949526 AA ...
Page 186: ...Security 6 9 Logout FST020 Function manual 184 Function Manual 09 2017 A5E42949526 AA ...
Page 188: ...Language 7 1 Language FST020 Function manual 186 Function Manual 09 2017 A5E42949526 AA ...
Page 192: ...Index FST020 Function manual 190 Function Manual 09 2017 A5E42949526 AA ...
Page 193: ......