Available parameters for
constant duct pressure
Unit configuration
BACnet object
R/RW
Note
Duct pressure nominal
PSuNom,
AVAL,119
RW
Pa; Maximum duct pressure of the unit
Duct pressure minimum
PDuctMin
AVAL,198
RW
Pa
Minimum fan speed
FanSpdMinRel
AVAL,201
%
Fan speed feedback fault
limit
FanSpdFbFltLm
AVAL,197
RW
%
Allowed tolerance time fan
speed feedback fault supply
fan = startup delay time
step 7
TiSttUpSpdVnt
PINTVAl,104
RW
Tolerance time = TiSttUpSpdVnt –
5 sec, maximal 60 sec
Allowed tolerance time fan
speed feedback fault exhaust
fan = startup delay time
step 6
DlyOnAflEhSta
PINTVAL,129
RW
Tolerance time = DlyOnAflEhSta –
5 sec, max. 60 sec
Selection of active sensor
PSenCnf
MVAL,150
1 = Both sensors (default)
2 = P4 supply air
3 = P5 exhaust air
Ramp up / down time of fans
TiRmpFanSuSpd
PINTVAL,98
RW
s
5.5.3.1 Available parameters for the supply fan (constant duct
pressure)
Available parameters for
supply fan
Current state
BACnet object
R/RW
Unit/Note
Present pressure setpoint
supply
SpPSu
AVAL,193
R
Pa
Present pressure supply
PSu
AVAL,460 (POS9)
AVAL,459 (QBM)
R
Pa
Supply fan speed
Prio 2: Fire / Smoke
Prio 5: Protection
FanSuSpd
A1: AO,102
A2: AO,111
A3: AO,120
A4: AO,129
Modbus: AO,149
RW
%
Supply fan speed feedback
FanSuSpdFb
Tacho:AI,65
0~10V:AI,96
Modbus: AI,163
R
%
Exhaust fan fault
FanEhFlt
Modbus: BI,144
R
Present flow supply
AirFlSu
AVAL,204
R
m3/h, available, if DiffPFanSu is
configured
Supply fan pressure diff.
DiffPFanSu
AVAL,17 (POS9)
AVAL,459 (QBM)
R
Pa, available, if DiffPFanSu is
configured
Application functionalities
Fan speed control
5
70 | 170
A6V10733786_en_c