Outputs A1, A2, A3, A4
Parameter
BACnet object
Selection for A1
A1Sel, STR_VIEW,264
Selection for A2
A2Sel, STR_VIEW,266
Selection for A3
A3Sel, STR_VIEW,268
Selection for A4
A4Sel, STR_VIEW,270
Selection
BACnet object
R/W
Signal type
Range
None
-
-
-
Supply air fan speed
FanSuSpd
R/W
0…10V
0…100 %
Exhaust air fan speed
FanEhSpd
R/W
0…10V
0…100 %
Preheating coil electric position
PreHclElPos
R/W
0…10V
0…100 %
Heat exchanger bypass damper position
HExgDmpBypPos
R/W
0…10V
0…100 %
Rotary heat exchanger speed
RotHExgSpd
R/W
0…10V
0…100 %
Heating coil electric position
HclElPos
R/W
0…10V
0…100 %
Heating coil valve position
HclVlvPos
R/W
0…10V
0…100 %
Cooling coil valve position
CclVlvPos
R/W
0…10V
0…100 %
Cooling coil DX evaporator position
CclDxPos
R/W
0…10V
0…100 %
Output Y1
Parameter
BACnet object
Selection for Y1
Y1Sel, STR_VIEW,68
Selection
BACnet object
R/W
Signal type
Range
None
-
-
-
Preheating coil electric position
PreHclElPos
R/W
PWM Triac
(pulse period
10s)
0…100 %
Heating coil electric position
HclElPos
R/W
PWM Triac
(pulse period
10s)
0…100 %
A-Alarm indication output
AalmIndOut
R/W
DO Triac
NO
B-Alarm indication output
BalmIndOut
R/W
DO Triac
NO
Common alarm indication output
CmnAlmIndOut
R/W
DO Triac
NO
Operation indication output
OpIndOut
R/W
DO Triac
NO
Configuration
Configuring the hardware
4
A6V10733786_en_c
45 | 170