4 Configuration
The configuration of the application can be executed in the configuration mode of
the ABT Go app. or in the configuration part of ABT Site.
4.1 Wireless connection with POL903
The WLAN USB stick dongle POL903 offers wireless access to the controller, for
example, via ABT Go.
The WLAN dongle can only be used temporarily since it is not been designed to be
used 24/7. Use the Ethernet port for a permanent wireless connection.
TIP: In those cases where the WLAN dongle is always plugged in the controller,
switch off USB power via BACnet, Modbus or Onboard input.
Available parameters
Actual values
BACnet object
R/RW
Note
USB supply power
switch
USBPowerIn
BI,148 (D1)
BI,149 (D2)
R
Push button
IP address
NwkPortIP
RW
Basic settings
BACnet object
R/RW
Note
USB supply power
setting
USBPower
BVAL, 352
RW
Initial configuration
1. Connect POL903 with POS3.5715 device on the USB port.
2. Power on POS3.5715 device
3. The WLAN signal is available after 5 minutes (phone or PC).
4. The default WLAN name is
Siemens-WLAN-Stick
and default password is
SIBPAdmin
5. The address for the WLAN Stick configuration is https://10.123.45.1:441
6. After connecting the WLAN, change the password and remember it.
Note: Click "Save" when making changes to "Settings" page, and then "Apply &
Restart".
Restart the POL903 for the configuration to take effect.