4.4 Selecting the device connections
Peripheral devices as well as room operating units and additional room sensors
must be activated (set to "Active") in the basic configuration before they can be
used in the application. As soon as a device is set to active, it can be connected
and further configured.
Activated KNX / PL-Link devices must be connected before powering the
controller, otherwise the device will not be recognized.
Modbus devices can be connected any time before power up or during run time.
Because of auto-connect and KNX power supply the number of room operator unit
and room sensors is limited, see "PL-Link [➙ 145]".
4.4.1 Peripheral devices
Available devices
●
POS9.1515/100 Modbus input/output extension module with 2 pressure
sensors, 2 inputs, 2 outputs.
●
2 x QBM97 Modbus (duct) air pressure sensors with 2 pressure sensors,
2 inputs, 2 outputs each.
Activating the devices
Peripheral devices
BACnet object
Selection
Note
Selection for I/O extension
device POS9
Pos9Sel,
STR_VIEW, 341
None (default)
No device
Active
Modbus device POS9 connected.
(communication is monitored)
Selection for duct pressure
device QBM97 #1
Qbm97Sel(1),
STR_VIEW, 344
None (default)
No device
Active
Modbus device QBM97 connected.
(communication is monitored)
Selection for duct pressure
device QBM97 #2
Qbm97Sel(2)
STR_VIEW, 413
None (default)
No device
Active
Modbus device QBM97 connected.
(communication is monitored)
Selection for EBM Papst
modbus fans
ModbSuFanSel
STR_VIEW, 469
None (default)
No device
Active
Modbus device Supply and exhaust air fans connected
(communication is monitored)
If the communication with the device can’t be established or gets lost, individual
alarm is triggered.