5.5.3.2 Available parameters for the exhaust fan (constant duct
pressure)
Available parmeters for
exhaust fan
Current state
BACnet object
R/RW
Unit
Present pressure setpoint exhaust
SpPEx AVAL,234
R
Pa
Present pressure exhaust
PEx
AVAL,457 (POS9)
AVAL,462 (QBM)
R
Pa
Exhaust fan speed
Prio 2: Fire / Smoke
Prio 5: Protection
FanEhSpd
A1: AO,103
A2: AO,112
A3: AO,121
A4: AO,130
Modbus: AO,150
RW
%
Exhaust fan speed feedback
FanEhSpdFb
Tacho:AI,69
0~10V:AI,97
Modbus: AI,164
R
%
Exhaust fan fault
FanEhFlt
Modbus: BI,145
R
Present flow exhaust
(Available if DiffPFanSu is configured)
AirFlEh
AVAL,223
R
m3/h
Exhaust fan pressure diff
(Available if DiffPFanSu is configured)
DiffPFanEh
AVAL,20 (POS9)
AVAL,461 (QBM)
R
Pa
Operating mode settings
BACnet object
R/RW
Unit
Unoccupied: extract
SpPExUcd
AVAL,285
RW
Pa
Economy: extract
SpPExEco
AVAL,284
RW
Pa
Comfort: extract
SpPExCmf
AVAL,283
RW
Pa
Fire: exhaust
SpPExFplc
AVAL,76
RW
Pa
Kitchen hood: extract
SpPExKtch
AVAL,286
RW
Pa
Special settings
BACnet object
R/RW
Unit
Exhaust fan Kp
GainAirFlEhCtr
AVAL,231
RW
%/Pa
Exhaust fan Tn
TnAirFlEhCtr
PINTVAL,122
RW
S
K-factor, exhaust fan
AirFlEhCoef
AVAL,236
RW
M3/h per Pa
Tacho signal mapping
Property 4965
FanSuSpdFb
Al,65
RW
Pulses/sec for 100% fan
speed
Range 0…300 pulse/s
Application functionalities
Fan speed control
5
72 | 170
A6V10733786_en_c