5.8.2 Supply air regulation with outdoor temperature compensa-
tion
During hot summer periods or cold winter times, supply air temperature setpoint
may be weather compensated to increase comfort and cost-optimize the operation.
Compensation can be activated individually for summer and/or winter with
dedicated supply air setpoint increase/decrease. The function is activated when
positive or negative setpoint shift (points 3 and 6) is set.
Outdoor temperature compensation is active when shift (3 or 6) is set to a value
other than 0. Outdoor-compensation affects both constant and cascade
temperature control.
Outdoor compensation affects the supply air temperature setpoint when used with
supply air temperature control.
It affects the room or extract temperature setpoint when used with cascade
temperature control.