Basic settings
BACnet object
R/RW
Note
De-icing mode configuration
DeicModCnf
MVAL,408
RW
1: None
2: Erc fix
3: Erc fix + Fans
4: Erc fix + Preh
5: Erc fix + Fans + Preh
6: Erc TEh
7: Erc TEh + Fans
8: Erc TEh + Preh
9: Erc TEh + Fans + Preh
De-icing, stage1 limit, heat exchanger
SpTDeicHExg
AVAL,177
RW
°C
De-icing, stage2 limit, fan
SpTDeicFan
AVAL,173
RW
°C
Activation time de-icing
TiDeic
PINTVAL,90
RW
sec.
De-icing rotor speed
HExgSpdDeic
AVAL,178
RW
%
De-icing supply fan flow
SpAirFlSuDeic
AVAL,181
RW
m3/h
De-icing exhaust fan flow
SpAirFlEhDeic
AVAL,226
RW
m3/h
De-icing supply fan pressure
SpPSuDeic
AVAL,196
RW
Pa
De-icing exhaust fan pressure
SpPExDeic
AVAL,232
RW
Pa
De-icing supply fan speed
SpFanSuSpdDeic
AVAL,208
RW
%
De-icing exhaust fan speed
SpFanEhSpdDeic
AVAL,238
RW
%
Special settings
BACnet object
R/RW
Note
Temperature drop for room extract
humidity of 20% r.h.
DiffTHuCmpDeic
AVAL,176
RW
K
Temperature for maximum off time
TDeicTiOffStt
AVAL,179
RW
°C
Maximum off time
TiOffDeicMax
PINTVAL,91
RW
sec.
Temperature for minimum off time
TDeicTiOffEnd
AVAL,180
RW
°C
Minimum off time
TiOffDeicMin
PINTVAL,92
RW
sec.
Application functionalities
Energy Recovery
5
A6V10733786_en_c
95 | 170